4�- START-UP
Once the unit is installed you must carry out the following start-up sequence for it to work prop-
erly.
4.1.- AUTOMATIC MODE
If the unit is going to operate in automatic mode, see Section 5.2.- AUTOMATIC. The start-up
sequence is:
1�- Put the mode selector switch in Manual Mode (OFF).
2�- Lift the RCCB cover.
3�- Put the RCCB contact in ON mode.
4�- Lower the RCCB cover.
5�- Put the mode selector switch in Automatic Mode (ON).
Note: The switch has an M2 hole where you can attach a seal or a padlock to block ac-
cess to the RCCB and any other attempts at manual reclosing (Figure 10).
Figure 10: Switch's M2 hole to seal access to the RCCB�
4.2.- MANUAL MODE
If the unit is going to operate in manual mode, see Section 5.1.- MANUAL. The start-up se-
quence is:
1�- Put the mode selector switch in Manual Mode (OFF).
2�- Lift the RCCB cover.
3�- Put the RCCB contact in OFF mode.
4�- Lower the RCCB cover (optional).