10 Instruction manual Getest 3.- Switch on the circuit breaker (6). The red led will light. 4.- Turn the safety key to the “ENABLED” position. Th
11 Instruction manual Getest 8.- Type the Maximum Defect Current (16) in order to calculate the step and contact voltage. Select to measure with a
12 Instruction manual Getest Connections Ground to test Metallic parts Min. 40 m Auxiliary ground 20 m 20 m Contact voltage 1 m Min. 40 m Auxil
13 Instruction manual Getest Ground Resistance Note about auxiliary ground: The auxiliary ground must be good enough for performing a proper meas
14 Instruction manual Getest Connecting to a PC Using a PDA to control the MPC unit allows to store all data in the PDA memory, and transfer them t
15 Instruction manual Getest Error and warning messages Error message Cause Solution Error:Reading cal data. Loading default data Corruption on
16 Instruction manual Getest Danger: loop resistance too high, possible connection error. Check connectons and ensure nobody is touching the injecti
17 Instruction manual Getest Specifications Mains supply Voltage 230V+/-20% 50-60Hz Current 15A AC Note: Required low impedance in mains supply l
18 Instruction manual Getest ETSI EN 301 489-17 EN61000-3-2, EN61000-3-3 EMC compliancy Device is compliant with EU LVD 2006/95/EC and EMC 89/336/EE
19 Instruction manual Getest Notes
2 Instruction manual Getest
20 Instruction manual Getest CIRCUTOR S.A. Vial Sant Jordi s/n - 08232 - Viladecavalls (Barcelona) Spain Tel: (+34) 93 745 29 00 Fax: (+34) 93 745
3 Instruction manual Getest Features - Step and contact meter, based on injection of current during 1 mains cycle - Supply up to 50A
4 Instruction manual Getest
5 Instruction manual Getest 10 Connect 12 Current to inject 15 1K Ohm resistor 17 Start sequence 19 Results tab 11 COM port 13 Mains frequency 16 M
6 Instruction manual Getest 30 Save data button
7 Instruction manual Getest Safety Electrical Shock This device may generate voltages that may be harmful to the body or cause death. Several pro
8 Instruction manual Getest Heavy weight Weight of the device is 45kg. This weight may be harmful to the body if not lifted by trained persons,
9 Instruction manual Getest Operation instructions 1.- Plug measure connections (2) and current connections (3) depending on the measure that is go