Circutor OPTIM HYB Series Uživatelský manuál Strana 13

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 36
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 12
2.1.2. CPC2 PANEL: ZERO SWITCHING CONNECTION CONTROL BY TWO SIN-
GLE-PHASE STAGES
The static capacitor banks come equipped with CPC2 panels in the single-phase stages.
The role of the CPC2 panels is to control the zero switching connection of the thyristor-diode
modules that operate the single-phase stages, preventing connection current transients.
The typical connection diagram of a step can be seen in Figure 6 and with more detail in section
“7.- OPTIM HYP type diagram”.
The CPC panels are activated via a 12 Vdc signal supplied by the Computer HYB regulator's
outputs. The standard CPC2 panels are designed to always be used between phase and neu-
tral on networks with phase-neutral voltage of Umax = 254 V.
Th-D 1
PPPC1
1 3
2
Q
1
U1
U2
1
32
4
5
Radiador
PLACA
1G1
+
-
CPC2
CONTROL
1K1
12VDC
Alimentación Potencia
Conexión a Condensador Monofásico
Mando
Figure 6: Basic connection diagram of the CPC2 to the power block.
13
Instruction Manual
OPTIM HYB Series
Zobrazit stránku 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 35 36

Komentáře k této Příručce

Žádné komentáře