2) setting of the decimal point position (00000., 0000.0, 000.00, 00.000,
0.0000); the button shifts the decimal point to the left, howe-
ver the button shifts the decimal point to the right;
The pressure of the button during the change of the parameter
value will cause the resignation of the write.
Table 1
InP 1
Para-
meter
symbol
Description Range of changes
tYP1
Selection of measured value
Cntr – number of pulses
FrEqL – frequency for
(f < 10 kHz)
FrEqH – frequency for
(f > 10 kHz)
tACH – rotational speed
PEr – period
PErH – long period > 10 s.
CntH – worktime counter.
Hour – current time
Enc – incremental encoder
SCAL1
Selection of input quantity rescaling. Mea-
sured value is multiplied or divided by the
set point value (parameter ConS).
And – multiplication by the
constant
diu – division by the constant
ConS1
Constant rescaling the input quantity.
The write of a negative value causes
the counting down (mode of pulse
counter and worktime counter).
-19999...99999
t_L1
Minimal duration time of the low level
pulse on the main input. The intro-
duction of a value lower than 0.25 or
5 causes the switching of the length
control function of the low signal level
off. The value is given in milliseconds.
0...60000