4�10�3�5� Power status�
TAll the Modbus map addresses are hexadecimal.
The 0x04 function is implemented for this variable.
This variable indicates the quadrant in which the unit is operating.
Table 21:Modbus memory map: Power status
Power status
Variable Address Default value
Power status 7D1 -
The variable format is shown in Table 22:
Table 22:Variable format: Power status�
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 1: Capacitive 1: Inductive 1: Generated 1: Consumed
4�10�3�6� Unit conguration variables.
All the Modbus map addresses are hexadecimal.
The 0x04 and 0x10 functions are implemented for this variable.
The unit’s Modbus function does not check whether the variables recorded are within the
correct margins, they are only checked when they are read from the EEPROM. So if any
parameter is recorded with an incorrect value the unit will be congured with its default value.
The Modbus conguration will not take effect until the unit is reset.
4�10�3�6�1� Transformation ratios�
Table 23:Modbus memory map: Transformation ratios�
Transformation ratios
Configuration variable
(1) (2)
Address Valid data margin
Default
value
Voltage primary 2710 - 2711 1 - 599999 1
Voltage secondary 2712 1 - 999 1
Current primary 2713 1 - 10000 5
Current secondary 2714
1: .../1A
5: ../5 A
5
(1)
All variables must be programmed at the same time.
(2)
Voltage ratio x Current ratio < 600000.
Note: The ratio is between the primary and the secondary.
67
Instruction Manual
CVM-C10