7.3.4.2.- Manual programming of transistor digital outputs
The following functions are implemented for these variables:
Function 0x04:reading registers.
Function 0x10: Writing multiple registers.
Table 90: Modbus memory map: Manual programming of outputs, expansion modules (Table 1).
Manual programming of transistor digital outputs
Configuration variable Valid data window Default value
Programming status
(1)
0: Automatic
1:Manual
0
Value
0: Open
1:Closed
0
(1)
When programming the Programming status manually set the output for the transistors manually, using the
Value parameter. The conguration of the transistor digital outputs programmed in the unit no longer works.
The transistors work in automatic mode according to the conguration programmed in the unit.
Table 91: Modbus memory map: Manual programming of outputs, expansion modules (Table 2).
Manual programming of transistor digital outputs: Slot 1
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status C428
C43C C450 C464 C478 C48C C4A0 C4B4
Value
C429
C43D C451 C465 C479 C48D C4A1 C4B5
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
Table 92: Modbus memory map: Manual programming of outputs, expansion modules (Table 3).
Manual programming of transistor digital outputs: Slot 2
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status C810
C824 C838 C84C C874 C874 C888 C89C
Value
C811
C825 C839 C84D C875 C875 C889 C89D
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
Table 93: Modbus memory map: Manual programming of outputs, expansion modules (Table 4).
Manual programming of transistor digital outputs: Slot 3
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status CBF8
CC0C CC20 CC34 CC48 CC5C CC70 CC84
Value
CBF9
CC0d CC21 CC35 CC49 CC5D CC71 CC85
Note: The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
235
Instruction Manual
CVM-B100 - CVM-B150