5.6.16.2.- Impulse mode of transistor digital output
When selecting the impulse mode, Figure 132, the conguration parameters are:
The variable code that controls the transistor.
The energy meter factor.
The high and low impulse period.
Figure 132: Conguration screen of transistor digital outputs (impulse mode).
The parameter selected is indicated in white.
It is possible that the unit may measure energy exceeding its conguration. Make
sure the energy pulses correspond to the maximum energy level admitted by the
installation.
To program the transistor digital output, after conguring the variable code and the pulse time
(with the low period and high period parameters), the following formula provides a method for
calculating the number of output pulses according to the generated energy so that the pulses
do not accumulate.
3600 * PE / PT > MP → PE = MP * TP / 3600
Where:
MP : Maximum power of the installation in W.
PE: Pulse energy in Wh ( Energy meter factor )
TP : low period + high period, in seconds.
For example: If the installation can consume 100kW, a suitable conguration could be pulses
of 10W ( Energy meter factor) with a high and low period of 50 ms.
The following options appear in the lower area:
158
CVM-B100 - CVM-B150
Instruction Manual