48
Measured value Indication range Measuring range Basic error
Current 1 A 0.000...12 kA 0.005...1.200 A~ ±0.2%
5 A 0.000... 60 kA 0.025...6.000 A~
Voltage L-N
100 V 0.0...0.48 MV 0.5...120 V ±0.2%
400 V 0.0 ...1.92 MV 2.0...480 V
Frequency 45.00...100.00 Hz 45.0...66.0...100 Hz ±0.2%
Active power -19999... 99999 MW - 2.88 kW...1.40 W...2.88 kW ±0.5%
Reactive power -19999 Mvar...0.00
...99999 Mvar - 2.88 kvar...1.40 var...2.88 kvar ±0.5%
Apparent power 0.00...99999 MVA 1.40 VA... 2.88 kVA ±0.5%
Coefficient PF -1...0...1 -1...0...1 ±0.5%
Tangens j
i
-1.2...0...1.2 -1.2...0...1.2 ±1%
j 0...359 0...359 ±1%
Active energy 0...9 999 999.9 kWh 0...9 999 999.9 kWh ±0.5%
Reactive energy 0...9 999 999.9 kvarh 0...9 999 999.9 kvarh ±0.5%
Current time 0.00...23.59 0.00...23.59 1 second
/24 h
Ku – voltage transformer ratio: 0.1...4000.0
Ki – current transformer ratio: 1...10000
8. TECHNICAL DATA
Measuring Ranges
Table 8
Relay outputs l relays, voltageless NOC contacts
load-carrying capacity 250 V/0.5 A
l relays, voltageless switched contacts
load-carrying capacity 250 V/0.5 A
(DHB-324)
Analog output (DHB-324) l current programmable 0/4...20 mA
load resistance 500 W
l voltage programmable 0...10 V
load resistance ³ 500 W
l galvanically isolated
l resolution 0.01% of the range