Code 8 bit binary, hexadecimal 0-9, A-F.
2 hexadecimal characters contained in each 8-bit field in
the message.
Bits per byte 8 data bits.
Field Check-Error CRC Type (Cyclical Redundancy Check).
Modbus functions used:
Function 01 Reading the status of the relays.
Function 03 and 04 Reading n Words (16 bits-2 bytes). Function used for
reading the electrical parameters that the
CVM-MINI
is
measuring. All electrical parameters are long with 32 bits,
because of this two Words are required to request each
parameter.
(4 bytes - XX XX XX XX)
Function 05 Writing a relay.
6.1 MODBUS memory map
PARAMETER SYMBOL
Instant Maximum
Minimum Units
Voltage phase
V L1
00-01 60-61 C0-C1
V x10
Current
A L1
02-03 62-63 C2-C3
mA
Active power
kW L1
04-05 64-65 C4-C5
w
Reactive power
Kvar L1
06-07 66-67 C6-C7
w
Apparent power
kV·A L1
4A-4B AA-AB 10A-10B
Power factor
PF L1
08-09 68-69 C8-C9
x 100
Voltage phase
V L2
0A-0B 6A-6B CA-CB
V x10
Current
A L2
0C-0D 6C-6D CC-CD
mA
Active power
kW L2
0E-0F 6E-6F CE-CF
w
Reactive power
Kvar L2
10-11 70-71 D0-D1
w
Apparent power
kV·A L2
4C-4D AC-AD 10C-10D
w
Power factor
PF L2
12-13 72-73 D2-D3
x 100
Voltage phase
V L3
14-15 74-75 D4-D5
V x10
Current
A L3
16-17 76-77 D6-D7
mA
Active power
kW L3
18-19 78-79 D8-D9
W
Reactive power
Kvar L3
1A-1B 7A-7B DA-DB
W
Apparent power
kV·A L3
4E-4F AE-AF 10E-10F
w
Power factor
PF L3
1C-1D 7C-7D DC-DD
x 100
Temperature
ºC
50-51 B0-B1 110-111
ºC x 10