56 Instruction Manual
Do not use the Temporary mode (2) if the supplier has not
recommended this for their installation. This method can cause
resonance in certain installations.
Power limit
This parameter allows the maximum power of the active filter to be limited. The
value is configured as a percentage with respect to the unit's nominal power. The
minimum configurable value is 20%, and the maximum is 100%.
Parallel Modules :
Access to the configuration screen of the number of active filters set out in
parallel with the same load (Figure 57).
Figure 57: Parallel module configuration screen.
A maximum of 8 AFQ-4W units can be installed in parallel, with different power
ratings.
All of the AFQ-4W must use the same load transformer. Refer to the
section 3.6.- PARALLEL CONNECTION OF 2 TO 8 ACTIVE FILTERS
to install more than one active filter in parallel.